2mm self leveller resin

Anti-static, hygienic, easy-to-clean self smoothing resin floor finish providing a hard wearing, seamless, anti-static floor compliant with BS 2050.

Used in dry process areas where the floor is subjected to medium to heavy duty foot, trolley, pallet truck and rubber wheeled fork lift traffic. Typical uses include laboratories, clean rooms, warehouses, and electronic, aerospace, automotive and printing plants.

  • Attractive, enhances working environment
  • Meets BS 2050 anti-static requirements
  • Hygienic – easy to clean
  • Non-tainting, non-dusting
  • Hard wearing floor finish
  • Abrasion resistant
FeRFA Resin Flooring guidelines

Description:

Applied in two or more coats. Generally solvent or water borne.

Duty:

light foot traffic, occasional rubber tyred vehicles.

Typical Thickness:

up to 150 µm

Description:

Applied in two or more coats. Generally solvent free.

Duty:

light foot traffic, occasional rubber tyred vehicles/regular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys

Typical Thickness:

150 µm to 300 µm

Description:

Applied in two or more coats. Generally solvent or water borne.

Duty:

lregular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys

Typical Thickness:

300 µm to 1000 µm

Description:

Aggregate dressed systems based on multiple layers of floor coatings or flow-applied floorings, often described as ‘sandwich’ systems.
MD/HD

Duty:

regular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys/constant fork lift truck traffic, hard plastic wheeled trolleys, some impact

Typical Thickness:

> 2 mm

Description:

Often referred to as ‘self-smoothing’ or ‘self-levelling’ flooring and having a smooth surface.

Duty:

regular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys/constant fork lift truck traffic, hard plastic wheeled trolleys, some impact

Typical Thickness:

2 mm to 3 mm

Description:

Trowel-finished, heavily filled systems, generally incorporating a surface seal coat to minimize porosity.

Duty:

regular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys/constant fork lift truck traffic, hard plastic wheeled trolleys, some impact

Typical Thickness:

> 4 mm

Description:

Having a smooth surface.

Duty:

constant fork lift truck traffic, hard plastic wheeled trolleys, some impact/severe heavily loaded traffic and impact

Typical Thickness:

4 mm to 6 mm

Description:

Trowel-finished, aggregate filled systems effectively impervious throughout their thickness.

Duty:

severe heavily loaded traffic and impact

Typical Thickness:

> 6 mm

Product: Page Flow ESD Finish: Gloss

Thickness: nominal 2 mm

Colour: Preparatory work and application in accordance with suppliers instructions.

Supplier: Page Industrial Coatings Ltd.

Telephone: Customer Service – +44 (0) 1443 475 270

Substrate Requirements
Concrete or screed substrate should be a minimum of 25N/mm2 , free from laitance, dust and other contamination. The substrate should be dry to 75% RH as per BS 8204 and free from rising damp and ground water pressure. If no damp proof membrane is present Hydraseal DPM can be incorporated directly beneath the Page Flow ESD system.

Primer :
1 coat Flowprime@ 0.25 kg/m,
2 coat Flowprime@ 0.25 kg/m,

Conductive Grid of 10 mm wide copper tape.
Anti-Static Primer: Peran ESD Primer@ 0.4 kg/m, Topping: Peran ESD SL (density 1.8 kg/I)@ 3.6 kg/m,
Detailed application instructions are available upon request.

Conductive Grid

A network of 10 mm wide, self-adhesive, conductive copper tape is always recommended in combination with any Page anti-static flooring system. The copper tape must be applied directly onto the cured final coat of Pageprime, 150mm in from the perimeter of the application. A further grid of tape should be applied within this area at 3 m centres. Special attention should be paid to tape areas passing over expansion or bay joints to ensure permanent electrical continuity. The applied tape matrix should be secure and fully bonded to a confirmed earth point.

Installation Service
The installation should be carried out by trained personnel of Page Industrial Coatings Ltd

The finished system is assessed as non-hazardous to health and the environment. The long service life and seamless surface reduce the need for repairs, maintenance and cleaning. Environmental and health considerations are controlled during manufacture and application of the products by Page staff and fully trained experienced contractors.

Focus on the Floorzone
Page are market leaders in specialist industrial and commercial flooring. Systems available include: underfloor heating systems, floor screeds, surface damp proof mem­branes, decorative floor finishes, seamless terrazzo, car park deck waterproofing, tank lining systems… to name just a few. Our objective is to satisfy your Floorzone needs.

The figures that follow are typical properties achieved in laboratory tests at 20°C and at 50% Relative Humidity:

Fire Resistance BS476: Part 7 Surface spread of flame: Class 2 (indicative)

Slip Resistance Dry >40 low slip potential Method described in BS 7976-2
(typical values for 4-S rubber slider) in accordance with HSE and UKSRG guidelines)

(The slipperiness of flooring materials can change significantly, due to the installation process, after short periods of use, due to inappropriate maintenance, longer-term wear and/ or surface contaminants (wet or dry).

Textured systems are recommended to meet slip resistance value requirements for wet conditions and/ or surface contaminants (wet or dry) – please contact our Technical Advisors for further details and specifications.

Temperature Resistance: Tolerant up to 60°C

Water Permeability: Nil – Karsten test (impermeable) Vapour Permeability 0.4 gms / m, / 24 hours

Surface Hardness: 180 secs. Koenig Hardness Test

Chemical Resistance: Contact Technical Department

Abrasion Resistance: Taber

Abrader: BS8204-2: Class AR2 50mg loss per 1000 cycles (1kg Load using H17 wheels) Compressive Strength 60 N/mm, (BS6319) Flexural Strength 40 N/mm, (BS6319)

Tensile Strength: 25 N/mm, (BS6319)

Bond Strength Greater than cohesive strength of 25N/mm, concrete. >1.5 MPa.
Electrical Resistance 5 x 10, – 1 x 10, O (to BS 2050)
1.8×10, -1.4×10. 0 (to EN 1081)

Speed Of Cure

10°C 20°C 30°C
Light Traffic 36 hours 24 hours 12 hours
Full Traffic 72 hours 48 hours 24 hours
Full Chemical Cure 10 days 7 days 5 days

Toxicity taint free to sensitive foodstuffs. Complies with BS 8204-6/FeRFA type 5

Cleaning and Maintenance
Clean regularly using a single or double headed rotary scrubber drier in conjunction with a mildly alkaline detergent.

Page’s products are guaranteed against defective materials and manufacture and are sold subject to its standard Terms and Conditions of Sale, copies of which can be obtained on request.